Post Buy Requirement
FI
United States
Add Review

Our Products

Reel Lite

  • Hose Size 1”
  • Coupling Bowl Size 1-3/16”
  • Proof Test Pressure (psi) 600
  • Proof Test Pressure (psi) 300
  • Weight per 50ft Length (uncoupled) 7 lbs
This specification covers the construction and performance criteria for Reel-Lite Booster hose suitable for a proof test pressure of 600 PSIG.

JACKET CONSTRUCTION:
The hose shall be of a single jacket construction.
The jacket shall be made with virgin spun polyester warp yarn woven in a twill weave and it shall be treated with yellow or red Wear Guard treatment.

LINING:
The hose shall be polyurethane lined and the lining material shall be suitable for potable water (when so ordered).

HYDROSTATIC PRESSURE TESTS:
The hose shall have a service temperature range of -60 F to 140 F.
The hose shall have a minimum service test pressure of 300 PSIG.
The hose shall have a minimum proof test pressure of 600 PSIG.
The hose shall have a minimum burst pressure of 900 PSIG. Some manufacturers state 1800 psi or more burst pressure. Reel-Lite is as safe as any competitors, but we feel 900 psi burst is more realistic. Based on testing, failure will come at the coupling before the hose. No 1 coupling is rated to withstand 1800-2000 psi.
The hose shall have a kink radius of no greater than 4.5 and a kink diameter no less than 9.

DIMENSIONS:
The hose shall not weigh more than 20 lbs. per 100 uncoupled.
The coil diameter on a standard 12 reel (100) is 18 inches.

COUPLINGS:

The hose shall be coupled with hardcoat aluminum expansion ring couplings.

Field repairable couplings available.

QUALITY ASSURANCE PROVISIONS:

Quality Standard: Hose is designed and tested to meet NFPA 1961 (current edition) Standards on Fire Hose. The fire hose furnished under the terms of this proposal has a potential service life of ten years, barring mistreatment or accidental damage that would render the hose unfit for service. The manufacturer shall be ISO 9001-2008 Quality Certified.

WARRANTY:

The manufacturer warrants the hose to be free from defects in materials and workmanship for a period of one year. This warranty shall provide for the repair or replacement of hose and couplings proven to have failed due to faulty material or workmanship.

CONSTRUCTION

*Single Jacket-100% High Tenacity Polyester Cover

*Circular Woven with Helical Inner Reinforcement

*Polyurethane Liner

*Expansion Ring Couplings or Field Repairable Couplings

*Protective Treated Color-Wear Guard, Yellow or Red



APPLICATIONS

*Designed for Wildland Use

*Grass and Brush Fires

*Wildland Fires

*Industrial Use

*Dumpster Fires

Reel-Lite may be used for other applications but may have limitations that should be taken into consideration



PERFORMANCE FEATURES

*Lightweight

*Flexible with Helix Reinforcement

*Low Drag Resistance

*Fully Loaded, Ready on Reel

*Can be used on a Standard 12 Reel Drum

*Should be kept charged on reel
Firequip_ReelLite
Reel Lite Booster Lightweight
Woven TPU Lined Forestry Reel Hose
Construction Applications

Single Jacket 100% High Tenacity Polyester Cover
Circular Woven with Helical Inner Reinforcement
Polyurethane Liner
Expansion Ring Couplings or Field Repairable Couplings
Protective Treated Color Wear Guard, Yellow or Red



Grass and Brush Fires
Wildland Fires
Dumpster Fires
Industrial Use

Performance Features Standard Length

Lightweight
Flexible with Helix Reinforcement
Low Drag Resistance Coefficient
Fully Loaded, Ready on Reel
TPU Liner has Low Kink Resistance
One-Year Warranty

50, 100

Hose Size Coupling Bowl Size Proof Test Pressure (psi) Service Test Pressure
(psi) Burst Test Pressure
(psi) Weight per 50ft Length (uncoupled) Weight per 100ft Length (uncoupled)
1 1-316 600 300 900 7 lbs 14 lbs
Quality Assured
ISO 9001-2008 Certified
# 9062QM8001
NFPA Member
Oil And Gas Website
Visit Our Oil And Gas Fracking Website
Categories

Accessories
Booster Hose
Forestry Hose
Hard Suction Hose
Industrial Hose
Municipal Fire Hose
New Products and Specials
Supply Line
View Complete Details

Wildland Ultra Forestry

  • Hose Size 3/4 “
  • Coupling Bowl Size (inches 1-3/16”
  • Proof Test Pressure (psi) 600
  • Service Test Pressure (psi) 300
  • Burst Test Pressure (psi) 900
=Scope

This single jacket 600lb. proof test Forestry Hose is designed for use with portable gasolinediesel pumps, heavy duty Fire Engine Tankers and Pumpers. Light in weight, this hose is made to be transported by air, man-packed or by animal for long distances over steep and rough forested areas. All components of the hose system shall be fabricated from mildew resistant material permitting storage over extended periods of time in damp areas without concern for degradation or deterioration. All components shall be made in the USA.

Quality

The fire hose to be supplied under this specification is a premium quality, single jacket forestry fire hose. All materials used in the fabrication of the hose shall be of the best quality commercially available. The manufacturer shall be ISO 9001-2008 Quality Certified.

Jacket Construction

The 100% synthetic warp yarn shall be virgin fiber domestically produced to be free from defects, dirt, knots, lumps and irregularities of weave as is consistent with quality manufacturing. The filler yarn shall be all polyester filaments, high strength material suitable in all respects for the manufacture of high quality fire hose. The jacket shall be constructed using a twill weave design to reduce friction loss and increase gallons per minute (GPM) flow due to the water way being smooth. Traditional square weave design is Not Acceptable and will be cause for the hose to be rejected.

Lining Construction

The thermoplastic lining shall be a single-ply extruded tube, compounded to reduce deterioration by ozone. The finished form shall be free of pits or other imperfections and shall have a smooth finish. No reclaimed material shall be used. The thickness shall not be less than .016 nor greater than .020 for the 1 hose and not less than .018 nor greater than .022 for the 1- hose. Tensile Strength not less than 1200 psi Elongation not less than 400%. Adhesion shall be such that a 12 lb. weight shall not move a 1- strip cut transversely at greater than 1 per minute.

Hydrostatic Tests

Each length of hose shall be capable of a hydrostatic pressure of 600 psi for fifteen (15) seconds, without leaking in the hose or at the couplings or breaking any yarn in the jacket. Burst of a 3 ft. specimen selected from every 5000 shall with stand without failure a pressure of 900 psi, or three times the Service Test Pressure of 300 psi while lying straight or curved to a radius of 27. Kink pressure shall be such that a random length of every lot of 2500 shall withstand without failure a hydrostatic pressure of 450 psi, or 1- times the Service Test Pressure of 300 psi while in a kink condition.

Hose Length and Diameter

The hose shall be available in nominal 50 and 100 foot lengths. The hose shall have an inside diameter of not less than the trade size of the hose.

Couplings

Hose is available with internal expansion ring anodized aluminum couplings with NH, NPSH, or Quarter Turn couplings, meeting U.S. Forestry specifications.

Warranty

The manufacturer warrants the hose to be free from defects in materials and workmanship for a period of one year. This warranty shall provide for the repair or replacement of hose and couplings proven to have failed due to faulty material or workmanship.
white2
Single Jacket
Thermo-Polyurethane Lined
Construction Applications

Outer Jacket 100% Polyester Yarn with Filament Polyester Filler Yarns
Lining Extruded thermo-polyurethane, compounded to resist ozone
Protective Treated Coating: WearGuard
Color: Yellow
Untreated White Available 187 Type I
Specification 187, meets USDA FSS 5100-187 Type 1



Brush, Grass and Forestry Fires
Designed for use with portable pumps, heavy duty pumps and tank trucks
Wildland Applications

Performance Features Standard Length

Premium Quality, long lasting hose
Mildew Resistant No drying required
Lightweight Designed to be carried by back pack or my hand for long distance over steep or rough terrain and forest conditions
Color Impregnation for greater abrasion resistance, heat resistance, reduced water absorption
Non-weeping (weeping hose available upon request)
Wildland available in 34 with garden hose threads. Yellow WearGuard treated 100 3 lbs.
One-Year Warranty
View Complete Details

Attack Lite Poly

  • HOSE SIZE 1 ½”
  • PROOF TEST PRESSURE (PSI) 800
  • SERVICE TEST PRESSURE (PSI) 400
  • BOWL SIZE 1 15/16”
  • WEIGHT PER 50 FT UNCOUPLED 12
Fire hose is one of the most important tools used by the fire department. As such, the following specification must be strictly adhered to unless the proposed specification exceeds specification listed. Only the fire department can determine if a proposed product meets and exceeds these specifications.

TECHNICAL INFORMATION:

NFPAISO Standard: The hose must meet all the requirements of NFPA 1961, Standard on Fire Hose (Current Edition). The manufacturer of the hose shall be ISO 9001-2008 quality certified.

Jackets: The jackets shall be evenly and firmly woven, free from unsightly defects, dirt, knots, lumps, and irregularities of twist that might affect the serviceability of the finished product. Each jacket shall be seamless and shall have polyester filler yarns woven around the hose throughout its length, with the warp ends interwoven with the warp yarn covering the filler yarns.

Warp ends of both the inner and outer jackets shall be high-tenacity filament polyester developed, designed and processed for the fire hose jacket filler yarns. The use of any warp yarns of filament or entangled construction is expressly forbidden.

Filler yarns of both the inner and outer jackets shall be high-tenacity filament polyester developed, designed, and processed for fire hose jacket filler yarns. These filament polyester yarns shall be free from defects that are unsightly or may affect the serviceability of the finished hose. The staple polyester warp ends must completely cover and protect the filament polyester filler yarns. The inner jacket shall be woven with a reverse twill weave to provide a smoother waterway.

Wear Guard: When specified, is a treatment for maximum abrasion resistance. This is a specially developed impregnated coating with a built in flame retardant. Wear Guard is applied to the outer jacket by a mechanical process which increases abrasion resistance by 6 times over standard impregnation. It greatly increases heat and flame resistance, almost eliminates water pickup and adds superb resistance to petro chemicals and displays extreme resistance to bacterial and mildew growth. Wear Guard Colors Red, Yellow, Tan, Orange, Blue, Forest Green.

Lining: The thermoplastic lining shall be a single ply extrusion of thermo-polyurethane polymer which naturally resists hydrolysis, ozone, and oxidation. Natural or synthetic rubber is Not Acceptable. The surface must be smooth and free from corrugations. No reclaimed material or through the weave extrusion lining shall be used. The lining material shall meet the requirements of the National Sanitation Foundation Standard 61 for potable water use. The lining thickness shall be tightly controlled to reduce weight, compactness and kink radius.

Ozone resistance: Lining specimens shall be subjected to ASTM D 1149-91, Standard Test Method for Rubber Deterioration- Surface Ozone Cracking in a Chamber. Specimens shall be prepared in accordance with ASTM DS 18-86, Standard Test Method for Rubber Deterioration- Surface Cracking Procedure C and shall be elongated 15%. Ozone Concentration shall be 100+-5 parts per hundred million by volume. Temperature shall be 40.0 +1.0 (104 F). Time shall be 100 hours. There shall be no appearance of cracking or crazing when viewed under a 7 power magnifying glass at any time during or at the end of the 100 hour exposure.

Accelerated Aging: Lining specimens shall be subjected to ASTM D573-88, Standard Test Method for Rubber Deterioration in an Air Oven.: Specimens shall be exposed to 70+- 1 C temperature for a duration of 166 +- 2 hours and shall be allowed to rest for 24 +- hours before testing. The tensile strength and ultimate elongation of the rubber lining after aging shall not be less than 75 percent of the original tensile and elongation.

Adhesion: the adhesive must be of uniform thickness around the circumference of the lining. The adhesion shall be such that the rate of separation of a 1 strip of lining, transversely cut, shall not be greater than 1 per minute under a weight of 18 lbs.No exceptions.

Low Temperature Flexibility: The hose shall be capable of performing in sub-zero conditions. A 3-foot section of hose shall be exposed to a temperature of -54 +- 2 C (-65 +- 3 F) for a period of 24 hours. At the end of the exposure period and while maintained at the -55C exposure temperature, the hose shall be rapidly bent 180 double on itself, first one way and then the other. There shall be no cracking or breaking of the jacket or liner. Leakage shall be cause for rejection.

Hydrostatic Test: Hydrostatic tests shall be conducted on hose equipped with the couplings to be delivered in accordance with NFPA 1961. Each length of hose is to be subjected to a hydrostatic proof test pressure on 800 PSI for at least 15 seconds and not more than 1 minute. Higher test pressures, which may weaken the hose, are expressly forbidden.

Twist: The hose shall not twist more than 4 turns per 50 ft. for the 1, 1 and 2 sizes, and not more than 1% turns per 50 ft. for the 2 and 3 sizes under a pressure of 800 PSI. No final twist in a direction to loosen the couplings shall be permitted.

Warp: The hose shall not warp more than 20 from a straight line drawn from center to center of the fittings at the ends of the hose and the hose shall not rise from the table.

Expansion: The expansion in circumference of the hose between 10 and 800 PSI shall not exceed 8%.

Elongation: The elongation between 10 and 800 PSI shall not exceed the burst pressure.

Burst Test: a 3-foot sample of hose chosen at random shall withstand, without failure, a hydrostatic pressure of 1200 PSI while lying straight or curved on a 27 radius. Retention of the coupling to the hose shall equal or exceed the burst pressure.

Kink Test: A full length shall withstand, while kinked, without failure, a hydrostatic pressure of 600 PSI.

Diameter: The hose shall have an internal diameter of not less than the trade size of the hoes, except that internal diameter of the 2 hose shall not be less than 2 916.

Method of Testing: All measurements and test to determine compliance of the fire hose with specified requirements shall be made in accordance with ASTM D 380-87 (Standard Test Methods of Rubber Hose), except as otherwise specified. All tests shall be conducted at the point of manufacture or at a laboratory equipped for such testing. All tests shall be performed as specified in NFPA 1961 (2007 Edition). Hydrostatic tests shall be conducted under controlled conditions employing equipment capable of supplying a uniform pressure.

Service Life: The fire hose furnished under the terms of this proposal has a potential service life often years, barring mistreatment or accidental damage that would render the hose unfit for service. Upon delivery, the fire hose shall be in first-class condition free from defects in workmanship and materials. The supplier shall provide replacement of any such hose as may be defective without any charge whatsoever to the Fire Department.

Warranty: The manufacturer warrants the hose to be free from defects in materials and workmanship for a period of TEN years. This warranty shall provide for the repair or replacement of hose and couplings proven to have failed due to faulty material or workmanship.
Firequip_AttachLitePoly1
Double Jacket Polyester
Ultra Lightweight
Thermo-Polyurethane Lined (TPU)
Construction Applications

Inner and Outer Jackets 100% High Tenacity Spun Polyester
Lining Thermo-Polyurethane (TPU) Liner Bound with Inner Woven Jacket
Wear Guard Treated Coating: Impregnated by a mechanical process to provide a total saturation of a synthetic polymeric treatment, heat fused within and on the outside of the woven jacket. The coating provides superior abrasion, heat, flame, and chemical resistance while reducing water absorption
NFPA 1901 Pump Panel Colors: Yellow, Red, Orange, Blue, Forest Green, Tan, Black (Limited Inventory), White (TreatedUntreated)



Number One Preference for High Rise Packs
Industrial and Municipal Fire Fighting
Master Stream Appliances
Municipal Potable Water Transfer
CrashFire Rescue
All Cold Weather Applications. -55F
Relay Pumping for Rural Water Supply

Performance Features Standard Length

Flow Characteristics: Low friction loss
LightweightSpace Saving: Requires Less Space than Standard Double Jacket or Rubber Hose
Reduces Firefighter Fatigue in High Rise Conditions with Easier Handling
Protective Color Impregnation: Immediate Line Identification and Communication Between Pump Operator and Nozzle Man
Tightly Woven Fabric: With reduced thickness liner, hose folds flat and tight in hose bed. Tight weave enhances abrasion resistance, fights kinking
Meets and exceeds all NFPA requirements for Fire Hose, current edition
View Complete Details

Full Flow Tough Heavy Duty Hose

  • Hose Size 1 ¾”
  • Bowl Size 2 1/8”
  • Proof Test Pressure (psi) 800
  • Service Test Pressure (psi) 400
  • Burst Test Pressure (psi) 1200
STATEMENT: FireQuip Full Flow is a tough heavy duty hose but lightweight that provides very low friction loss with maximum flow. It is manufactured with 100% tightly woven polyester yarn making it tough and abrasion resistant. The special lining process that welds the lining directly to the yarn while being woven creates an inseparable bond without adhesives. The waterway is smooth, filling in the corrugations of the weave, which results in low friction loss, with more water to the fire at lower pump pressure. Full Flow is light and compact but yet extremely heavy duty. FireQuip Full Flow puts greater volumes of water to the fire without over-working the firefighter or the fire engine.

SPECIFICATIONS

Fire hose is one of the most important tools used by the fire department. As such, the following specification must be strictly adhered to unless the proposed specification exceeds specification listed. Only the fire department can determine if a proposed product meets and exceeds these specifications.

Quality: The fire hose to be supplied under this specification is a premium quality, double, jacket municipal fire hose. All materials used in the fabrication of the hose shall be of the best quality commercially available. The manufacturer of the hose shall be ISO 9001-2008 quality certified.

Service Life: The fire hose furnished under the terms of this proposal has a potential service life of ten years, barring mistreatment or accidental damage that would render the hose unfit for service. Upon delivery, the fire hose shall be in first-class condition free from defects in workmanship and materials. The supplier shall provide replacement of any such hose as may be defective without any charge whatsoever to the Fire Department
View Complete Details

Big Water

  • Hose Size 7 ¼”
  • Service Test PSI 300
  • Proof Test PSI 600
  • Burst Kink Test PSI 900
  • Weight 100ft Uncoupled 163 lbs
The 7 , 8 and 10 LDH to be supplied under these specifications is specifically designed to supply extra large volumes of water at high pressure with minimal friction loss to oil refinery and large storage tank fires. Tough and ready for action, but light in weight and strong, compact and practical, and will fit on most hose storage devices.

The hose shall be of double jacket construction with 100% virgin spun polyester yarn in both jackets. There shall also be a minimum of 10.0 filler yarns per inch in both the inner and outer jackets. The Warp shall be 15D polyester for outer jacket and the Weft shall be 11D polyester for the inner jacket. The thickness of the liner shall be 0.22 minimum and shall be constructed of TPU elastomer. Our liner process produces an amazingly thin but smooth inner waterway, yielding an extremely low friction loss for maximum flow.

The outer hose jacket shall be mechanically impregnated with specially developed Wear Guard treatment, which greatly increases abrasion resistance, heat and flame resistance, practically eliminates water absorption and adds superb resistance to petro chemicals that are commonly found around oil refineries and tank farms. Wear Guard also adds extreme resistance to bacterial and mildew growth. The Wear Guard color shall be high visibility Safety Yellow.

The hose temperature range shall be -60F to 150F.

Taber abrasion test minimum of 100, 000 cycles and FM abrasion test minimum of 65, 000 cycles.

Elongation shall not exceed 14% at 300 PSI, the warp shall be no more than 6 and shall not rise from test table and shall not twist more than turn per 100 at 300 PSI.

Factory hydrostatic test shall be conducted on hose equipped with the couplings to be delivered in accordance with NFPA 1961. Each length of hose is to be subjected to a hydrostatic proof test pressure of 600 PSI for the 7 , and 400 PSI for the 8 and 10, for at least 15 seconds and no longer than 1 minute.

The Storz couplings shall be manufactured of 6061-T6 extruded aircraft aluminum with stainless steel bolts and locks and shall be hardcoat anodized. Cast or forged aluminum is not considered to meet this specification and is not acceptable. Couplings shall be manufactured in the USA.
View Complete Details

Tank Flex

  • Hose Size 2 ½ ”
  • Bowl Size 3 “
  • Working Pressure PSI 150
  • Burst PSI 450
  • Weight per 10ft Length (uncoupled) 16
OUTER JACKETS (COVER AND TUBE) MADE OF SYNTHETIC EPDM RUBBER
LINER HAS A SPECIAL WIRE HELIX AND NYLON FABRIC REINFORCEMENT
CONSTRUCTED WITH SOFT CUFF ENDS FOR GREATER COUPLING RETENTION
SMOOTH COVER AND INNER LINER
10 FOOT STANDARD LENGTHS

APPLICATIONS

DRAFTING FROM ANY RURAL OR MUNICIPAL NON-PRESSURIZED WATER SOURCE
DESIGNED SPECIFICALLY FOR RURAL FIRE DEPARTMENTS EASE OF HANDLING
MUNICIPAL WATER SUPPLY TRANFER

PERFORMANCE FEATURES

MORE FLEXIBLE THAN MOST STANDARD HARD SUCTION HOSE FOR EASIER AND FASTER HOOKUP
TOUGH AND DURABLE CAN WITHSTAND PRESSURE IF REQUIRED
DESIGNED FOR FULL VACUUM OZONE RESISTANTNO PLASTIC COUPLINGS
MEETS OR EXCEEDS NFPA STANDARD 1961, CURRENT EDITION
MANUFACTURER MUST BE ISO 9001-2008 QUALITY CERTIFIED
FIVE YEAR WARRANTY
View Complete Details

Maxi Flex PVC

  • Hose Size 1.5″
  • Working Pressure psi (68 °F) 70
  • Working Pressure psi (104 °F) 45
  • Weight per 10ft Length(uncoupled) 5
CONSTRUCTION

The original pvc lightweight suction only hose

Special corrugated pvc exterior for maximum flexibility and smooth waterway

Clear flexible pvc between the helix ribs for full vision of water

Distinctive black colored helix ribs for maximum uv protection

One piece extruded aluminum field repairable, reattachable collars on couplings

Collars are aluminum, not plastic which is subject to temperature extremes

the manufacturer shall be iso 9001-2008 quality certified

APPLICATIONS

Drafting from any rural or municipal non-pressurized water source

Designed for suction only!

Pvc hose shall not be used on pressurized hydrants or for relay pumping.

this is not a supply hose for hydrant use.

Limit exposure to direct sunlight for long periods of time.

PERFORMANCE FEATURES

ULTRA FLEXIBLE AND LIGHTWEIGHT, ONE-MAN HOOK-UP OPERATION IF NECESSARY

DESIGNED FOR FULL VACUUM CLEAR HOSE FOR FULL VISION OF WATER FLOW

TIME SAVING WITH LESS MANPOWER REQUIRED COMPARED TO CONVENTIONAL SUCTION HOSE

5, 2.5 and 3 COUPLED WITH EXPANSION RINGS NO PLASTIC COUPLINGS

4, 4.5, 5 AND 6 COUPLED WITH REATTACHABLE BOLT-ON COUPLINGS

(FOLDING LONG HANDLES AVAILABLE)

MEETS OR EXCEEDS NFPA STANDARD 1961, CURRENT EDITION FIVE YEAR WARRANTY
View Complete Details

Hydro Flow SDH

  • HOSE SIZE 1”
  • PROOF TEST PRESSURE (psi) 600
  • SERVICE TEST PRESSURE (psi) 300
  • BURST TEST PRESSURE (psi) 900
  • COUPLING BOWL SIZE (in.) 1-3/16”
GENERAL

Fire hose is one of the most important tools used by the fire department. As such, the following specification must be strictly adhered to unless the proposed specification exceeds specification listed. Only the fire department can determine if a proposed product meets and exceeds these specifications.

HOSE CONSTRUCTION

Hose meeting specification shall be made from 100% high tenacity synthetic yarn, circularly woven and completely protected and locked-in by a tough, highly resistant synthetic, extruded-through-the-weave nitrile rubber, forming a unitized construction without use of glues or adhesives of any type. Hose meets all requirements of NFPA 1961.

Lining Properties

Ultimate Tensile Strength of the lining and cover shall not be less than 1200 PSI. Ultimate Elongation shall be 400 percent minimum. Accelerated Aging Test consists of the tensile strength and ultimate elongation of the vulcanized rubber compound which has been subjected to the action of oxygen at a pressure of 300 PSI and a temperature of 158 degrees for a period of 96 hours while retaining 60 percent of its originally stated properties. Chemical Resistance:

Exposure to sea water and contamination by most chemical substances, hydrocarbons, oils, alkalis, acids, and greases must have no effect on the short or long term performance of the hose. A chemical resistance chart is available and Firequip Inc. will provide specific chemical resistance data on request for unique applications.

Color

Color shall be of HIGH VISIBILITY yellow or red. Other colors are available upon request.
View Complete Details

Hydro Flow LDH

  • HOSE SIZE 4”
  • PROOF TEST PRESSURE (psi) 500
  • SERVICE TEST PRESSURE (psi) 250
  • BURST TEST PRESSURE (psi) 750
  • COUPLING BOWL SIZE (in.) 4- 5/16”
GENERAL

Fire hose is one of the most important tools used by the fire department. As such, the following specification must be strictly adhered to unless the proposed specification exceeds specification listed. Only the fire department can determine if a proposed product meets and exceeds these specifications.

HOSE CONSTRUCTION: Hose shall be made from 100% high tenacity synthetic yarn, circularly woven and completely protected and locked-in by a tough, highly resistant synthetic, extruded-through-the-weave nitrile rubber, forming a unitized construction without use of glues or adhesives of any type. Hose meets all requirements of NFPA 1961, latest edition.
View Complete Details

Booster Hose

  • Hose Size ¾”
  • Working Pressure (psi) 800
  • Burst Test Pressure (psi) 3200
  • Coupling Bowl Size (in.) 1’-1/4”
  • Weight per 50’ Uncoupled 21 lbs
Fire hose is one of the most important tools used by the fire department. As such, the following specification must be strictly adhered to unless the proposed specification exceeds specification listed. Only the fire department can determine if a proposed product meets and exceeds these specifications

The Quick One

The hose that must be relied upon for fast and reliable fire attack before the small localized fire can grow out of control. Firefighters demand performance the first time and every time.

Pressure Contraction and Elongation When pressurized, a poorly constructed hose may contract or elongate. This can endanger a firefighter in a high place or in a tight spot. It can also damage equipment such as hose reels which can actually be crushed. FireQuip Booster Hose is made with precision reinforcement angles to control length change under pressure to avoid these problems.

Durable, Bright Red Cover It looks good and lasts longer for overall better cost effectiveness and reliability. The cover shall be EPDM rubber, which resists abrasion, gouging, ultra-violet, ozone aging and heat.

Long Lengths Firequip Fire Engine Booster Hose is produced in continuous lengths of 200 feet for 1 inch hose and 300 feet for inch. This reduces the number of coupling connectors required, reducing cost and increasing hose integrity.

Full 4:1 Safety Factor You must require a 4:1 safety factor for your booster hose to insure safety and reliability. This means 800 Booster Hose must be rated for 3200 minimum burst pressure. A lesser grade hose cannot be relied upon to handle pressure surges, end pull, kinking and other abuse, coupling retention and aging.

Meets UL 92 Design and Performance Criteria Firequip Fire Engine Booster Hose meets or exceeds the requirements listed in UL 92 specification for 800 PSI Booster Hose. The manufacturer shall be ISO 9001-2008 Quality Certified.
View Complete Details
Tell Us What are you looking for? Will call you back

Contact Us

  • (Firequip)
  • Burlington, NC 27217 map, United States
  • Share us via

( ! ) Warning: Cannot modify header information - headers already sent by (output started at /htmlcachedir2/dynamic-html-pages/eitempfilen/usa/company/firequip/products.htm:44) in /home/sgupta/exportersindia.com/htdocs/script-files/company-page/index.php on line 59
Call Stack
#TimeMemoryFunctionLocation
10.0005458000{main}( ).../index.php:0
20.01542048752include_once( '/home/sgupta/exportersindia.com/htdocs/script-files/country-vanity/country_index_page_common_script.php' ).../index.php:309
30.02492771504include_once( '/home/sgupta/exportersindia.com/htdocs/script-files/company-page/index.php' ).../country_index_page_common_script.php:282
40.03193711848header ( ).../index.php:59
ExportersIndia: 404 Error Found
404Oops! It seems this page is not available

We connect Buyers and Sellers

Tell us What you Need

Trending Categories

Find Suppliers by Region


View All Categories

Find Suppliers by Country

Waiting for permission
To search by voice, go to your browser settings and allow access to microphone

Allow microphone access to search with voice