The baghouse cleaning device (compressed air, fan or shaker) only operates when needed. The equipment operator adjusts the high differential pressure (dirtyclogged media) On Set Point and low differential pressure (cleaned media) Off Set Point. When the differential pressure rises to high it hits the On Set Point, then the baghouse cleaning device turns on and cleans the filter media until the differential pressure decreases to the Off Set Point, then the cleaning device automatically turns off saving energy and reducing equipment and filter media wear and tear. As the filter media slowly becomes clogged again the differential pressure raises up to the On Set Point and the cleaning cycle begins again.